Fluid machine project

via Freelancer ·

Budget / Salary$10–30
TypeFreelance project
LocationRemote
Posted5 hours ago
recent graduate from Bahrain polytechnic proposed the idea of installing a centralized chilled water plant to supply
air-conditioning units at GPIC. The concept is based on operating the chilled water system during nighttime, when
electricity demand and tariffs are lower and ambient air temperatures are cooler. Under these conditions, the refrigeration
system can achieve a higher coefficient of performance (COP), making chilled water production more energy-efficient.
The chilled water would then be stored and utilized during the daytime when cooling demand is at its highest.
As part of this system, chilled water must be transported from the central plant to various air-conditioning units
throughout the facility. To reduce engineering costs, GPIC has assigned the preliminary design work to undergraduate
students undertaking their industrial work experience at the plant. In this project, you will act as the design engineer.
Your design should include the following activities:
• Pipe material selection
• Pipe diameter selection
• Pressure drop calculations
• Centrifugal pump selection
• Check valve selection
• Venturi flow meter design
The detailed requirements are outlined below.
• You are to size the pipe lines and to select a suitable pump. The proposed piping layout is as per the attached
schematic.
• You are given details of the required lengths of pipes and the number of bends involved to get the chilled water
to each of the cooling coils. There are isolating valves around each piece of equipment so that maintenance work
can be carried out.
• Select the appropriate check valves which must be fitted before each coil at the supply lines according to all the
engineering parameters of the system.
• You have also been asked to design a venturi flow meter, a form of flow measurement device, to be installed after
the pump so that the total water flow can be measured on a continuous basis. You will need to demonstrate how
the venturi will work.

At the beginning of your presentation, include 1-2 slides describing the overall design and operation of a centralized
chilled water plant. The slides should:
• Identify the main components of the system (e.g., chillers, cooling towers, pumps, cooling coils, tanks, valves,
and piping).
• Explain the function of each component and how they work together.
• Include suitable diagrams or images obtained from reputable online sources, with proper referencing.
This section is intended to demonstrate your understanding of the complete chilled water system before presenting your
detailed design calculations and pump selection.
Step 1: Pipe Material Selection
Select a suitable pipe material for the chilled water distribution system. Consider the following factors:
• Operating temperature and pressure of the chilled water system
• Corrosion resistance
• Internal surface roughness
• Mechanical strength and durability
• Installation and maintenance requirements
• Cost-effectiveness
• Compatibility with chilled water applications
Compare at least two suitable pipe materials (eg carbon steel, galvanized steel, copper, stainless steel, HDPE or PPR)
and justify the final selection based on engineering and economic considerations.
Step 2: Pipe Diameter Selection
Using the required flow rates in the three cooling coils, determine suitable pipe diameters for:
• The three parallel branches
• The common supply and return lines
Select pipe sizes such that the flow velocity is close to the value assigned by the tutor.
Note: The tutor will assign a velocity range between 1.5 m/s to 2.5 m/s to differentiate individual student projects
Step 3: Hydraulic Loss Calculations
Calculate the hydraulic losses in each section of the system (parallel branches and common lines) by
• Applying Bernoulli’s equation
• Determining the flow regime (laminar or turbulent)
• Obtaining friction data for the selected pipe material
• Using the moody diagram to determine friction factors
• Calculating friction losses
• Using standard tables to determine losses due to fittings, valves, joints and bends
Note: The total pressure drop ΔP provided for each coil branch includes the pressure loss across the fan coil unit, which
is typically greater than the pressure losses in the piping system.
Step 4: Pump Selection
Select a centrifugal pump by determining
• Pump type
• Pump size
• Pump efficiency
• Required electric motor size
When calculating the pump total head, assume:
• The water levels in the chilled water supply and return tanks are equal.
• The three cooling coil branches operate in parallel
• Only the branch with the highest pressure drop (ΔP) needs to be considered.
Note: You may use the lecture notes for pump selection, or select a suitable pump from a reputable manufacturer's
catalogue available online. Ensure that the selected pump's specifications are included and properly referenced.
Step 5: Pump Performance Curves
Prepare the following graphs
• Flow rate versus pressure drop (head)
• Flow rate versus pump efficiency
• Input power on the same graph
Step 6: Final Pump Selection
The selected pump may not always operate at its Best Efficiency Point (BEP) due to changes in the water levels of the
chilled water supply and return tanks throughout the day.
Assuming:
• Static head = −8 m when the supply tank is full,
• Static head = 0 m when both tank levels are equal,
• Static head = +8 m when the return tank is full,
Determine the pump flow rate, total head, and efficiency for each condition. Briefly discuss how changes in static head
affect the pump operating point.
Step 7: Valve Selection
The provided piping schematic shows only the control valves. Review the system and identify locations where check
valves should be installed. Add the check valves to the schematic and briefly justify their placement based on the operation
of the chilled water system.
6
Discuss:
• Selection criteria
• Engineering considerations
• Final valve selection
• Roles and functions of the selected valves within the system
Step 8: Venturi Meter Design
Design a venturi meter to measure the total flow rate delivered by the pump.
Provide:
• A complete schematic drawing
• Relevant dimensions
• Design calculations
• Operating principle
• Expected efficiency
• Pressure loss characteristics
Step 9: Final Design Presentation
Present the complete system design with all relevant calculations and engineering justifications.
Step 10: References and Appendices
Include:
• All referenced tables and data sources
• Calculation details
• Intermediate design steps
• Supporting information
Presentation Requirements:
The presentation should clearly demonstrate the complete engineering design process and include:
• Executive Summary
• Introduction
• Pipe material Selection
• Pipe Diameter Selection
• Pressure Drop Calculations
• Pump Selection and Performance Curves
• Venturi Meter Design
7
• Check Valve Selection
• Final System Design
• Conclusions and Recommendations
• References
• Appendix (supporting calculations)
Considering the above points
• Prepare the presentation using Microsoft PowerPoint or any equivalent presentation software
• The presentation must contain a minimum of 25 slides and a maximum of 30 slides
project management engineering mechanical engineering computational fluid dynamics thermodynamics robot mechanical design